Table A.4 Oil Nozzle Press. Drop vs. Burner Heat Input
• Pressure drops for #2 Oil with 137,000 Btu/lb. gross heating value.
2
6421 8 10 20 40 60 80 100 200 300
4
6
8
10
20
40
60
6V
8V
10V
12V
14V
16V
18V
22V
24V
28V 36V
32V
Burner Gross Heat Input (MMBtu/hr.)
Oil Nozzle Pressure Drop (psig)
Table A.5 Atomizing Air Pressure Drop vs. Air Flow
• When air is used for atomization of heavy oil, it should be preheated to
approximately the same temperature as the oil.
10
60402010 80 100 1,000200 400 600
20
30
15
40
50
60
Atomizing Air Flow (SCFM)
Atomizing Air
Pressure Drop (psig)
8V
6V
10V 12V 14V 18V 22V 28V 36V
16V 24V 32V
A-4
Note:
Fuel pressure drop curves should be used as a guide for setting up
burner. It is recommended to use a direct fuel flow measurement
(orifice plate or flow meter) for calculating actual fuel flows.