Eclipse Vortometric v2.00 Guía de instalación Pagina 48

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 51
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 47
Eclipse Vortometric Burner v2.00, Installation Guide 248, 6/00
Table A.6 Atomizing Steam Press. Drop vs. Steam Flow
Atomizing steam must be dry and superheated a minimum of 20°F above
saturated at the atomizer inlet.
10
60402010 80 100 4,000200 400 600 1,000 2,000
20
30
15
40
50
60
Atomizing Steam Flow (lb/hr)
Atomizing Steam
Pressure Drop (psig)
8V
6V
10V 14V 18V 24V 32V
12V 16V 22V 28V 36V
RECOMMENDED
SPARE
PARTS
To make sure that the downtime of the system is as short as possible
in case of a failure, you should keep a stock of spare parts.
Recommended spare parts
PART NAME QTY. PART NO.
Pilot assembly 1 1
Spark rod assembly 1 1
Oil gun assembly 1 1
U.V. scanner (if used) 2 2
1-1/4" N.P.T. peepsight glass 2 13046
1-1/4" N.P.T. peepsight gasket 2 13047
1 Part number varies depending on burner size used.
2 Part number varies depending on U.V. scanner used.