Eclipse Vortometric v2.00 Guía de instalación Pagina 14

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 26
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 13
Eclipse AirHeat v2.00, Installation Guide No. 135, 7/99
14
Supply Piping
Locate the valve train close to the burner. The gas must
reach the burner during the fixed trial for ignition.
Sufficiently size shut off valves in the valve train.
Make sure piping is large enough.
Minimize piping elbows.
Pipe Connections
Installation of a pipe union in the gas line is recommended
to simplify burner removal.
Use of flexible pipe is optional.
Note:
Flexible pipe causes higher pressure drops than standard
pipe. Consider this when sizing your gas lines.
BURNER MOUNTING
(CONTINUED)
Piping Support
Use brackets or hangers to support the gas piping. If you
have questions, consult your local gas company.
Control Motor
Install a control motor to modulate the gas control valve if
not previously installed on the burner.
There are two different types of flame sensors:
U.V. scanner:
Each AirHeat burner is capable of U.V. flame monitoring. The
burner will not come equipped with a U.V. scanner. A ½”
NPT connection is provided on each AirHeat burner for the
connection of a U.V. scanner.
For detailed information on how to install and connect an
Eclipse U.V. scanner, refer to:
straight U.V. scanner; Bulletin / Info Guide 854
90° U.V. scanner; Bulletin / Info Guide 852
self-check U.V. scanner; Bulletin / Info Guide 856.
Installing the flame sensor
Flame rod:
If the flame rod option was selected when the burner was
ordered, the burner will be delivered with the flame rod
already installed on the burner
For detailed information on how to install and connect a
flame rod, refer to:
Bulletin / Info Guide 832.
Vista de pagina 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 25 26

Comentarios a estos manuales

Sin comentarios