Eclipse AirHeat v2.00, Installation Guide No. 135, 7/99
16
Adjustment, Start &
Stop
4
In this chapter you will find instructions on how to start and
stop a burner. The chapter begins with general instructions
that are useful for adjustment.
INTRODUCTION
d
Danger:
The AirHeat burners, described herein, are
designed to mix fuel with air and burn the
resulting mixture. All fuel burning devices are
capable of producing fires and explosions if
improperly applied, installed, adjusted,
controlled, or maintained.
Do not bypass any safety feature; fire or
explosion could result.
Never try to light a burner if it shows signs of
damage or malfunction.
BURNER ADJUSTMENT If you are adjusting an AirHeat burner for the first time, you
must follow these steps:
1. Reset the system
2. Set air flow
3. Ignite the burner
4. Set high fire gas
5. Set low fire gas
6. Verify gas settings
7. Stop Procedure
2. Close these valves
- the automatic gas valves
- the manual gas cocks
3. Start the combustion air blower
Step 1: Reset the system
1.
Start circulating duct fan.
Step 2: Set air flow
Measure the air pressure drop across the burner between Tap
“A” and Tap “C”. (See page 5 of Data 135.) Turn the disc on
the blower air inlet until the air pressure is between 0.6”w.c.
(1.5mbar) minimum and 1.2”w.c. (3.0mbar) maximum. For a
given input, lower air pressure drops will produce a longer
flame, and higher drops will produce a shorter flame with
slightly higher CO levels.