Eclipse AirHeat v2.00, Installation Guide No. 135, 7/99
23
PROBLEM POSSIBLE CAUSE SOLUTION
Air pressure drop/velocity is
too low.
Main flame is uneven along the
length of the burner.
Increase air pressure drop.
Poor air distribution in duct.
Check profiling and duct
obstructions.
Air wings are dirty, holes are
clogged.
Inspect and clean air wings if
necessary.
Main flame is yellow and long
at high fire.
Gas pressure too high at
burner inlet.
Check gas pressure against
design. Adjust main gas
pressure regulator.
Air pressure drop/velocity too
low.
Open air damper on
combustion air blower.
Air wings are dirty, holes are
clogged.
Inspect and clean air wings if
necessary.
CO emission is too high.
Burner is outside range
specified in Data 135.
Adjust burner settings.
Process air velocity exceeds
limits given in Data 135.
Bring velocity within limits;
adjust process air blower.