Eclipse AirHeat v2.00, Installation Guide No. 135, 7/99
15
To verify the system was properly installed, perform the
following checks:
1. Be sure there are no leaks in the gas lines.
2. Be sure all the components contained in the flame
monitoring and control system are properly installed.
This includes verifying that:
all the switches are installed in the correct locations.
all wiring and pressure lines are properly connected.
3. Be sure all components of the spark ignition system are
installed and functioning properly.
4. Be sure the blower rotates in the proper direction. If the
rotation is incorrect, have a qualified electrician rewire the
blower to rotate in the proper direction.
5. Be sure all valves are installed in the proper location and
correctly oriented relative to the flow direction.
CHECK LIST AFTER
INSTALLATION
PREPARE FOR
ADJUSTMENT
After installation of the burner system components is
complete, the following steps should be followed in order to
prepare for adjustment:
1. Set the air flow switch so that it drops out at 20% below
the maximum pressure of the combustion air blower.
2. Set the low gas pressure switch at 20% below the gas
pressure measured at the inlet to the main gas valve train.
3. Set the high gas pressure switch at 20% above the gas
pressure measured at the inlet to the main gas valve train.
4. Close all manual valves feeding the burner.
5. Try to ignite the burner before the purge and other timers
have finished their cycles. Make sure that the flame
monitoring system indicates a flame failure.
6. Trip out the pressure switches and other limit interlocks.
Make sure that the main gas valve train closes.
d
Danger:
If simulated limits or simulated flame failures do
not shut down the fuel system within the
required failure response time, immediately
correct the problem before proceeding.